Pepperl+Fuchs KFD2-HLC-Ex1.D Series Manual page 21

Hart loop converter
Hide thumbs Also See for KFD2-HLC-Ex1.D Series:
Table of Contents

Advertisement

HART Loop Converter KFD2-HLC-Ex1.D(.**)
Installation
Connection KFD2-HLC-Ex1.D.4S
The following connections are available:
Terminals 10/11: output I (relay 1 (NO contact))
Terminals 11/12: output II (relay 2 (NO contact))
Terminals 16/17: output III (relay 3 (NO contact))
Terminals 17/18: output IV (relay 4 (NO contact))
Terminals 7 ... 9: output V, current output as source (7/8) or sink (7/9)
Terminals 13 ... 15: output VI, current output as source (13/14) or sink (13/15)
Terminals 19 ... 21: output VII, current output as source (19/20) or sink (19/21)
Terminals 22/24: connection of HART handheld
Terminals 23/24: power supply 24 VDC
Figure 3.7
KFD2-HLC-Ex1.D.4S
mA
mA
250 Ω
mA
ERR
24 V DC
Power Rail
10
I
11
II
12
16
III
17
IV
18
7
V
8+
+
V
9-
-
13
VI
14+
+
V
15-
-
19
VII
20+
+
V
21-
-
22
23+
24 V DC
24-
Zone 2
Div. 2