Pepperl+Fuchs KFD2-HLC-Ex1.D Series Manual page 38

Hart loop converter
Hide thumbs Also See for KFD2-HLC-Ex1.D Series:
Table of Contents

Advertisement

HART Loop Converter KFD2-HLC-Ex1.D(.**)
Installation
Example
Characteristic 4 - 20 NE43, start value 2 bar, end value 10 bar
EN
20.5
20.0
Figure 3.8
Defining the Fault Current (fault message)
The type of fault current chosen will define how the current output transmits the fault
message to the controller.
1.
2.
3.
4.
5.
36 - EN
mA
4.0
3.8
0
1.9
2
Select the type of fault current using the  or  buttons.
Select the fault current down.
The fault message is indicated by a low current value.
Select the fault current up.
The fault message is indicated by a high current value.
Select the fault current hold.
The last measured value before the fault occurred is stored.
Confirm your entry with OK.
10.25
10
bar

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents