Hazardous Area Installations; Panel Mount - Siemens multiranger 100 Quick Start Manual

Sensor system
Hide thumbs Also See for multiranger 100:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1

Hazardous Area Installations

Note:
The following instructions apply only to the

Panel mount:

Instructions specific to hazardous area installations (Reference
European ATEX Directive 94/9/EC, Annex II, 1/0/6)
The following instructions apply to equipment covered by certificate number
SIRA06ATEXT9163X:
1.
For use and assembly, refer to the main instructions.
2.
The equipment is certified for use as Category 3D equipment.
3.
The equipment may be used in hazardous zone 22 except for conductive dusts (e.g.,
metal or carbon dusts).
4.
This equipment has a maximum surface temperature of T75 °C (in a +50 °C ambient).
Refer to the applicable Code Of Practice for selection of this equipment with respect
to specific dust ignition temperatures.
5.
The equipment is certified for use in an ambient temperature range of -20 to +50 °C.
6.
Any cable or conduit entries must meet the requirements of European Directive 94/
9/EC for Group II, Category 3D and maintain the overall IP rating of the enclosure.
7.
Cable should be selected in accordance with the applicable Code of Practice and
such that its insulation can withstand the maximum surface temperature of the
enclosure (T75 °C).
8.
The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
9.
Installation and inspection of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice (EN 60079-14 and EN
60079-17 in Europe).
10. Repair of this equipment shall be carried out by suitably trained personnel in
accordance with the applicable code of practice (e.g. EN 60079-19 within Europe).
11.
Components to be incorporated into or used as replacements in the equipment shall
be fitted by suitably trained personnel in accordance with the manufacturer's
documentation.
12. Manual override can be accomplished by using the disconnect switch provided in
the building installation.
7ML19985QD83
MultiRanger 100/200, product number 7ML5033.
MultiRanger – QUICK START MANUAL
Page EN-11