CleaverBrooks CEJS Installation, Operation And Maintanance page 42

Electrode boiler
Table of Contents

Advertisement

Electrode Boiler
Electrode positioning
• Space and center each of the electrode housings. The
bottom plate of the electrode bracket is fitted with
slots for front-back adjusting. Verify the electrode
housing is squarely facing the nozzle plates.
• Tighten electrode retaining nut until washers are
compressed to the appropriate specifications as
shown below in Figure 13. While tightening, have an
assistant inside the boiler verify that the electrode
boxes do not move. If boxes turn, check rod threads
for damage or nut binding. DO NOT forcefully restrain
boxes during tightening. Refer to Figure 13 below for
more details.
Figure 13 - Spring Washer Loading
38
750-272

Advertisement

Table of Contents
loading