Environment Requirements

MP2800 series routers must be used indoor. To guarantee stable use of
routers, the application scenario must meet the following requirements.
Temperature & Humidity
To ensure the service quality and life of MP2800 series routers, it is
recommended to maintain a certain temperature and humidity in the
computer lab. If the humidity in the computer lab is high for long time, it
causes the poor insulation and even electricity leak of insulation materials
easily.
Sometimes, the mechanical performances of materials change and the
metal parts are corroded easily, too. If the relative humidity is too low,
insulation
Meanwhile, in dry environment, static electricity appears easily, which
harms the circuits on the router.
If the temperature is too high, the reliability of the router reduces greatly.
The long-time high temperature affects the life and speeds up the aging of
insulation materials.
The recommended temperature and humidity in computer room:
Temperature
Long-term
15℃-30℃
Measuring points of the working temperature and humidity of MP2800
in the computer room mean the values measured from the floor above
1.5 m and 0.4 m from the front of the rack when there are no
protection boards.
The short-term working condition means less than 48h continuously
and less than 15 days for the annual total.
Extreme
temperature and humidity when the air-conditioning system in the
computer room fails. Each time the normal work should be recovered
within less than 5h.
Maipu Confidential & Proprietary Information
pads
shrink,
which
Short-term
0℃-40℃
adverse
working
causes
the
fastened
Relevant humidity
Long-term
40%-65%
environment
means
screws
loose.
Short-term
10%-90%
the
environment