 PZD
Name
Bit
RUN signal
0
FWD signal
1
REV signal
2
SU signal
3
OL signal
4
ZSW
IPF signal
5
FU signal
6
ALM signal
7
Command
8 to 14
count
15
HIW
0 to 15
0 : OFF
1 : ON (inverter running)
0 : OFF
1 : ON (forward rotation operation being
performed)
0 : OFF
1 : ON (reverse rotation operation being
performed)
0 : OFF
1 : ON (up to frequency)
0 : OFF
1 : ON (overload alarm)
0 : OFF
1 : ON (an instantaneous power failure or
undervoltage occurs)
0 : OFF
1 : ON (output frequency being detected)
0 : Inverter normal
1 : Inverter alarm occurrence
Command count
The command count is an optional feature maintained by the PROFIBUS master and can range from H00
to H7F.
The option unit copies the command count from the command it receives to the same byte offset in the
response it sends. The master may use this to synchronize commands and responses.
Not used (0 is returned)
Not used (0 is set)
Definition
• For master-to-slave messages (command request), bits 0
to 7 are not used and must be set to 0. The bit-wise data
here do not reflect Pr.190 to Pr. 196 (output terminal
function selection).
• At command response, signals are the same. Signals are
not affected by settings of Pr.190 to Pr.196 (output
terminal function selection).