(2) Loosen the terminal screw and insert the cable into the terminal.
Tighten each cable with fixing screws to the recommended tightening torque.
<Cable connection example>
Screw size
Tightening torque
M2
0.22 N•m to 0.25 N•m
NOTE
• Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short circuit or malfunction
due to damage to the screw or unit.
18
WIRING
D+ D-
V-
Cable size
2
0.3 mm
to 0.75 mm
<Connection example of multiple inverters>
To next inverter
D+ D-
D+ D-
V-
To master
Screwdriver
Small
flat-blade screwdriver
2
(Tip thickness: 0.4 mm /tip width: 2.5 mm)
V-