Mitsubishi Electric FR-A8NP Instruction Manual page 49

Hide thumbs Also See for FR-A8NP:
Table of Contents

Advertisement

Name
Fault
Power-on inhibit
Alarm
Control request
ZSW
FU signal
RUN signal
FWD
REW
NET mode
BUSY
HSW
HIW
48
PPO TYPE SUPPORT SPECIFICATION
Bit
0 to 2
Not used (1 is returned)
0: Inverter normal
3
1: Inverter alarm occurrence
4, 5
Not used (1 is returned)
6
0 is returned
Command execution normal
7
Command execution error
8
Not used (0 is returned)
9
1 is returned
0: OFF
10
1: ON (output frequency being detected) (Refer to Pr.42 and Pr.43 in the
Instruction Manual (Detailed) of the inverter.)
0: OFF
11
1: ON (inverter running)
0: Other than forward running (during stop, reverse running)
12
1: Forward running
0: Other than reverse running (during stop, forward running)
13
1: Reverse running
0: Other than network operation mode
14
1: Network operation mode
0: Ready status
15
1: Busy status

0 to 15
Set frequency (0.01 Hz increments)
0 to 15
Output frequency (0.01 Hz increments)
Definition
