6. Install sensor using the supplied sensor cable - spec.
NTC 15 kΩ @ 25°C.
▪ Press out the blanket located at the bottom of the
thermostat and insert the seal nipple.
▪ Connect sensor to terminals 6+7.
The sensor cable can be extended up to 50 m with 1.5
mm² installation cable without affecting the accuracy
of the thermostat.
Do not place the cable parallel to other installation ca-
bles as undesirable signals may be induced.
The installation must be permanent.
If the sensor is to be built in, used for pipe applica-
tions, or exposed to pressure, always install it in a con-
duit.
7. Turn on the power supply.