Single Outdoor Unit Installation; When The Upward Area Is Open; When An Obstruction Is Present Also In The Upward Area; Multiple Outdoor Unit Installation - Fujitsu WGYA050DG6 Design & Technical Manual

Hide thumbs Also See for WGYA050DG6:
Table of Contents

Advertisement

3-21
INSTALLATION PLACE

SINGLE OUTDOOR UNIT INSTALLATION

z

When the upward area is open

Obstacles at rear only
150
z

When an obstruction is present also in the upward area

Obstacles at rear and above only
1000
300
Max. 500

MULTIPLE OUTDOOR UNIT INSTALLATION

Provide at least 15 mm of space between the outdoor units if multiple units are installed.
When routing the piping from the side of an outdoor unit, provide space for the piping.
No more than 3 units must be installed side by side.
When 3 units or more are arranged in a line, provide the space as shown in the following example
when an obstruction is present also in the upward area.
z
When the upward area is open
Obstacles at rear only
250 or more
250 or more
Obstacles at rear and
sides only
200
300
200
Obstacles at front only
250 or more
250 or more
300
- (OU01 - 11) -
Obstacles at front only
1000 or more
Obstacles at rear, sides, and above only
250
Max. 500
250
Obstacles at front and rear only
250 or more
1500
or more
(unit: mm)
Obstacles at front and rear only
150
1000 or more
1500
500
250 or more
1500 or more
Outdoor unit / Single phase
500