SAFETY DEVICES
Circuit protection
Current fuse (Main PCB)
Fan motor protection
Thermal protecter
Thermal protection program
(Compressor temp.)
Compressor protection
Thermal protection program
(Discharge temp.)
Thermal protection program
(Heat exchanger temp.)
High pressure protection
Pressure sensor
Low pressure protection
Pressure sensor
(Cooling mode only)
Protection from
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
- (OU01 - 28) -
Model
WOÛK112LCTA WOÛK140LCTA WOÛK160LCTA
5A 250V
3.15A 250V
10A 250V
150±20ºC
Fan motor stop
120±20ºC
Fan motor restart
112ºC
Compressor stop
80ºC
Compressor restart
115 °C
Compressor stop
after 7 minutes
Compressor restart
68 °C
Compressor stop
63 °C
Compressor restart
4.2 MPa
Compressor stop
3.0 MPa
Compressor restart
0.12 MPa
Compressor stop
0.15 MPa
Compressor restart
Outdoor unit / 3 phase