Toshiba HWS-803XWHM3-E Service Manual page 68

Hide thumbs Also See for HWS-803XWHM3-E:
Table of Contents

Advertisement

Item
Basic operation logic
There are 4 operation combination pattern for Heating & Hot water
When open signal is input, the operation status change to the next status.
For example, if current operation status is heating ON and hot water OFF, then next status to be heating OFF &
hot water OFF when pulse is input Hydro unit memorize the status of the operation pattern before changing OFF
status by close signal.
If pulse is input at operation status 2, the operation pattern in the status 3 is same pattern in the status 1.
Manually ON/OFF
If customer change operation pattern manually by remote controller, change then operation pattern will not be
same as the basic logic.
1. If customer stop operation ( Heating off and hot water off ) by the controller, then both heating& hot water
are not to be ON with close or open signal.
2. If the unit is stopped ( Heating off and hot water off ) by open signal, operation pattern will be referred to
the pattern before the unit OFF by close signal.
• When you want to turn on/off with the pulse input reflec ting the operation setting on the remote control (hot water
supply, heating, or hot water supply and heating).
FC52="3", FC61="1"
Operation
status 1
Operation
status 2
Operation
status 3
Operation
status 4
There are 4 operation combination pattern for Heating & Hot water
When pulse signal is input, the operation status change to the next status.
For example, if current operation status is heating ON and hot water OFF, then next status to be heating OFF &
hot water OFF when pulse is input Hydro unit memorize the status of the operation pattern before changing OFF
status by pulse signal.
If pulse is input at operation status 2, the operation pattern in the status 3 is same pattern in the status 1.
If customer change operation pattern manually by remote controller, then operation pattern will not be same as the
basic logic.
1. If customer stop operation ( Heating off and hot water off ) by the controller, then both heating& hot water
to be ON with pulse input.
2. If the unit is stopped ( Heating off and hot water off ) by pulse input, operation pattern will be referred to
the pattern before the unit OFF by pulse.
Related FC
FC No.
52
61
Operation flow and applicable data, etc.
RC on condition
×
RC off condition
FC61=1 & FC52=3
Heating
Hot water
Heating
×
Hot water
×
Heating
Hot water
Heating
×
Hot water
×
Setting item
Control method
Object to control
67
Operation pattern
×
×
×
×
Pulse input
×
×
×
×
Pulse input
×
×
×
×
Pulse input
×
×
×
×
Default
0
0
Manually ON/OFF
change by remote
controller
Pulse input
Setting value
0-3 (See 8-1.)
0-3 (See 8-2.)