No.
Exchange parts name
13
Flow switch
14
Manometer
Work procedure
To replace a water circuit part, first close the water
supply source valve and the valve of water pipe
connected to the hydro unit.
1. How to remove
1) Perform the step 1-1 and step 5.
2) Remove the flow switch.
The flow switch connection uses an O ring for water
seal. Be careful not to scratch the O ring; otherwise,
water leakage may occur.
2. How to attach
1) Attach a new flow switch in the reverse order of the
removal.
NOTE
As shown on the right,
place a flow sensor parallel to the water heat exchanger
inlet pipe so that the wire is place on the right side from
the front view.
After the flow switch replacement repair, open the
water supply source valve and water piping valve to
pass water through the hydro unit, and check that
the flow switch connection has no water leakage.
To replace a water circuit part, first close the water
supply source valve and the valve of water pipe
connected to the hydro unit.
1. How to remove
1) Perform the step 1-1 and step 5 and 6.
2) Remove the manometer.
After the manometer replacement repair, open the
water supply source valve and water piping valve to
pass water through the hydro unit, and check that
the manometer connection has no water leakage.
Flow switch
Water heat inlet pipe
159
Remarks
Flow switch
Manometer