Toshiba HWS-803XWHM3-E Service Manual page 131

Hide thumbs Also See for HWS-803XWHM3-E:
Table of Contents

Advertisement

FC
52
External input contact logic (must be used in with
FC61)
54
Logic of 3-way valve's action when powered (Single
return only)
58
Night set back is activated
59
Interval of Mixing Valve control
5A
P1 setting while in hot water supply mode
5B
Boiler running setting
61
Changing the target of stopping/starting by external
signal or changing the TEMPO setting
62
Activate/deactivate A02 error detection
64
Continuously run or stop the P2 pump while cooling
65
P1 pump setting when the thermostat is deactivated in
the room temperature remote control and room
temperature thermostat settings
67
Changing the condition of optional output (For the
optional P.C. board connected to CN209)
92
Upper room temperature limit when cooling
93
Lower room temperature limit when cooling
94
Upper room temperature limit when heating
95
Lower room temperature limit when heating
96
Initial water temperature setting when controlling
cooling by the room temperature remote control and
room temperature thermostat
9D
Initial water temperature setting when controlling
heating by the room temperature remote control and
room temperature thermostat
9E
TO temperature setting to stop the P1 pump during the
middle period heating
*1 FC_01 is needed for PCB replacement or function code reset procedure has been completed.
*2 System restart with remote controller.
*3 Restart in the mode when stopping.
Item
Details
0000: CLOSE to stop system *2
0001: OPEN to stop system *2
0002: OPEN to stop system, CLOSE to restart
system (Statics input)
0003: CLOSE to stop system, CLOSE again to restart
system (plus input)
0000: Not reversed (Hot water mode when powered)
0001: Reversed (Heating when powered)
0000: Zone 1 & 2
0001: Zone 1 only
0001: 1 minute
-
0030: 30 minutes
0000: While running HP only
0001: P1 continues running
0000: Boiler and HP
0001: Boiler only
0002: Heater
0000: Hot water supply and heating
0001: Keeping initial status *3
0002: Hot water supply only
0003: Heating only
0004: TEMPO1 (Not activate the heaters)
0005: TEMPO2 (Not activate the heaters, inlet pump,
heat pump)
0000: Activate
0001: Deactivate
0000: Continuously run P2
0001: Stop P2
0000: Continuously run P1
0001: Stop P1 when the thermostat is OFF
0000: 1-3 During defrosting
2-3 While compressor is running.
0001: 1-3 As error is detected
2-3 During operation
0000: 15°C
-
0055: 30°C
0000: 15°C
-
0055: 30°C
0000: 15°C
-
0055: 30°C
0000: 15°C
-
0055: 30°C
0010: 10°C
-
0055: 25°C
0010: 20°C
-
0055: 55°C
0010: 10°C
-
0030: 30°C
130
First shipment
0000:CLOSE to stop
0000: Not reversed
(Hot water mode when
powered)
0000: Zone1 & 2
0004: 4 minutes
0000: Boiler and HP
0000: Hot water
supply and heating
0000: Activate
0000: Continuous
running
0000: Continuous
running
0000: 1-3 During
defrosting
2-3 While compressor
is running.
0029: 29°C
0018: 18°C
0029: 29°C
0018: 18°C
0020: 20°C
0020: 40°C
0020: 20°C