9-6-2. Outdoor unit
No.
Component name
Compressor
Type
DA220A2F-22L
(803H-E)
DA422A3F-25M
(1103,1403H-E)
DA422A3F-27M
(1103, 1403, 1603H8(R)-E)
1
Outdoor fan motor
Type
ICF-280-A60-1
(803H-E)
ICF-280-A100-1
2
(1103,1403H-E)
(1103 to 1603H8(R)-E)
4-way valve coil
Type
VHV-01AP552B1
3
STF-01AJ 502E1
Pulse motor valve coil
Type
CAM-MD12TF-15
(802H-E)
4
Type
UKV-A025 0100
(1103,1403H-E)
(1103 to 1603H8(R)-E)
Measure the resistance value of each winding with a tester.
Red
White
Black
Measure the resistance value of each winding with a tester.
Red
White
Black
Measure the resistance value.
803 to 1403H-E
1473 Ω ± 103 Ω
1103 to 1603H8(R)-E
1435 Ω ± 144 Ω
Measure the resistance value.
1 White
M
6 Red
3 Orange
Yellow
Blue
2
1 Black
M
6 Grey
3 Red
Yellow
Grey
Orange
2
6
125
Check procedure
803 to 1403H-E
Location
Red
White
White
Black
Black
Red
1103 to 1603H8(R)-E
Location
Red
White
White
Black
Black
Red
Location
Red
White
802H-E
White
Black
Red
White
1103,1403H-E
1103 to
White
1603H8(R)-E
Black
Location
Red
White, Orange
Red
Yellow, Blue
4
Location
Grey
Black, Red
Grey
Yellow, Orange
4
Resistance
value
1.04-1.16 Ω
1.04-1.16 Ω
1.04-1.16 Ω At 20°C
Resistance
value
0.75-0.83 Ω
0.75-0.83 Ω
0.75-0.83 Ω At 20°C
Resistance value
32.6 ± 3.3 Ω
Black
Red
14.8 ± 1.5 Ω
Black
Red
Resistance
value
42-50 Ω
42-50 Ω
Condition 20°C
Resistance
value
43-49 Ω
43-49 Ω
Condition 20°C