(2)-3. Sensor, Current, Compressor operation frequency, PMV position indication
The values detected by controller, such as temperature sensor or current values, can be easily checked.
Legend)
Item setting
TD
SW803
TH
SW803
LED indication
* TD, TL, and TH show errors below the ordinary temperature because they are sensors for high temperature.
* Current value for the outdoor unit only is shown.
Off
Light
----
----
Temperature sensor (
)
TE
TS
TO
SW803
SW803
SW803
TA
TC*
SW803
SW803
*Refer to page 147
less than -25
-25 - -21
-20 - -16
-15 - -11
-10 - -6
-5 - -1
0 - 4
5-9
10-14
15-19
20-24
25-29
30-34
35-39
40-44
45-49
50-54
55-59
60-64
65-69
70-74
75-79
80-84
85-89
90-94
95-99
100-104
105-109
110-114
115-119
120 or higher
sensor failure, not connected
Current
(A)
TL
SW803
SW803
0-0.9
1-1.9
2-2.9
3-3.9
4-4.9
5-5.9
6-6.9
7-7.9
8-8.9
9-9.9
10-10.9
11-11.9
12-12.9
13-13.9
14-14.9
15-15.9
16-16.9
17-17.9
18-18.9
19-19.9
20-20.9
21-21.9
22-22.9
23-23.9
24-24.9
25-25.9
26-26.9
27-27.9
28-28.9
29-29.9
30-30.9
31 or higher
149
Compressor
PMV position
operation
(pulse)
frequency
(r.p.s.)
SW803
SW803
0-4
0-19
5-9
20-39
10-14
40-59
15-19
60-79
20-24
80-99
25-29
100-119
30-34
120-139
35-39
140-159
40-44
160-179
45-49
180-199
50-54
200-219
55-59
220-239
60-64
240-259
65-69
260-279
70-74
280-299
75-79
300-319
80-84
320-339
85-89
340-359
90-94
360-379
95-99
380-399
100-104
400-419
105-109
420-439
110-114
440-459
115-119
460-479
120-124
480-499
125-129
500
130-134
-
135-139
-
140-144
-
145-149
-
150-154
-
155 or higher
-