Exchange parts
No.
name
6
Compressor
Compressor lead
Work procedure
2. Attach the compressor
1) Attach the compressor in the reverse order of the
removal.
NOTE
Be sure to replace the compressor lead after the
compressor replacement. (Compressor lead spare
parts code: 43160591)
At this time, wind the ferrite core with the
compressor lead for 4 times.
Attach the soundproofing board (Inward winding,
Outward winding), as shown in the right figure,
through between the compressor and between the
piping and parting board.
Fix the TD sensor with a commercially available
heat resistant binding tie through the piping cover
so that the sensor do not contact the discharge
pipe.
3) Vacuuming
1) Connect the vacuum pump to the charge port and
check joint of the gas piping valve to operate the
vacuum pump.
2) Perform vacuuming until the vacuum low pressure
gauge shows 1(mmHg).
NOTE
Open fully the pulse motor valve before vacuuming.
With the valve closed, vacuuming between the outdoor
unit liquid valve and the pulse motor valve may fail.
How to make pulse motor valve forcible full open
• Turn on the electric leakage breaker.
• Set the SW804 dip switch 1 and 3 on the outdoor
unit control board to ON.
• Press SW801 on the outdoor unit control board
for 1 second or longer.
• After pressing SW801 for 1 second or longer,
turn off the electric leakage breaker within 2
minutes.
4. Charge refrigerant
1) Add refrigerant whose amount is defined
according to the piping length from the valve
charge port. (HWS-1102H, 1402H : 2.7kg)
Compressor lead
Overlap soundproofing board
(Outward winding) at this position
Suction pipe
Do not make space between soundproofing boards
(Upper and Outward winding)
Rivet
Make the other end of the
line go through under the rivet
178
Remarks
Wind ferrite core with
compressor lead
for 4 times
Ferrite core
0 to 50
(Compressor lead positioning standard)
Place soundproofing board (Outward winding)
through between suction pipe and header pipe
Header pipe
Discharge pipe
Overlap soundproofing board (Inward winding)
at this position through between compressor,
outlet pipe, and suction pipe
Soundproofing
board (Upper)
Soundproofing board