8 Troubleshooting
53
Alarm code
-
IPM or Dip IPM and PCB2 have detecting function of abnormality. This alarm is indicated when the transistor mod-
ule detect the abnormality 7 times in 30 minutes including 7. Retry operation is performed up to the occurrence of
6 times.
Conditions:
The abnormal current such as short circuited, grounded or the overcurrent occurs at the transistor module.
The temperature at transistor module increases abnormally.
The control voltage decreases.
The angle difference between the shaft in compressor and the shaft in the control program exceeds +60deg.
268
SMGB0087 rev.0 - 12/2013

Activation of transistor module (RAS-(8-12)HN(P/C)(E))