8 Troubleshooting
RAS-(8-12)HN(P/C)(E)
Is fuse (EF1 or EF2)
of outdoor unit normal?
Yes
Remove the connector CN6 on
PCB1. Power source ON
Is LED2 (green) on
OU PCB1 flashing?
Yes
Reconnect the connector CN6 on
OU PCB1
Is LED2 (green) on
OU PCB1 flashing?
Yes
Does flashing speed
become faster than before?
Yes
Normal IPM.
Check the electrical wiring again.
Is LED2 (green) on
OU PCB1 flashing?
Yes
Does flashing speed
become faster than before?
Yes
Normal Inverter PCB.
Faulty fan motor.
  N O T E
Surely perform the troubleshooting of DC fan motor according to section
fan motor fails, the normal inverter PCB may be damaged.
233
SMGB0087 rev.0 - 12/2013
No
No (LED2 ON or OFF)
No (LED2 remains ON or OFF)
No
No (LED2 ON or OFF)
*1)
Is DC fan motor
No
normal?
Check it by troubleshooting at
item
Checking method of DC fan
motor for outdoor unit
Faulty Inverter PCB
Incorrect wiring
In case fuse melted,
Check the cause of
Faulty OU PCB1
Power source OFF
Remove the connectors
PCN201/202 and CN201/202 on
inverter PCB
Power source ON
Faulty inverter PCB
No
Faulty DC fan motor
Faulty inverter PCB
Yes
Normal
"8.4 Checking procedure for main
replace fuse.
melting
Incorrect wiring
8
parts". If the DC

Hide quick links: