CHIMNEY

Connection to chimney

• The stove meets the requirements for connecting to chimneys
dimensioned for flue gas temperatures of 350°C.
• The external diameter of the connection sleeve is 150 mm.
• The stove requires a draft in the chimney of at least –12
Pa. The draft is affected both by the length and area of
the chimney, and by how well sealed it is. The minimum
recommended chimney length is 3.5 m and suitable cross-
sectional area is 150-200 cm² (140-160 mm in diameter).
Rear connection to a masonry chimney
The back panel must be installed before the stove is connected at
the rear.
Ø
c a 1 8 0 m m
1
4
Ø
c a 1 8 0 m m
2
5
• A flue with sharp bends and horizontal routing reduces the
draught in the chimney. The maximum horizontal flue is 1 m,
on the condition that the vertical flue length is at least 5 m.
• It must be possible to sweep the full length of the flue and the
soot doors must be easily accessible.
• Carefully check that the chimney is sealed and that there is no
leakage around soot doors and flue connections.
In the bag with these installation instructions
are two wing screws for the cover.
3
6
Make sure that the connector
!
gasket does not come loose when
the connection pipe is placed on the
sleeve. If further sealing material is
required, heat-resistant sealant may
be used.