63 9810.0293 - Rev.00 - 08/09/2008
Both boiler back pressures and boiler pressures
must be in consideration at chimney calculations.
If the waste gas heat is under 160°C in
continuous operating, it is forbidden to use an ordinary
chimney.
Mount the flue gas connection pipe on to the
chimney with ascending slope. The flue gas pipe must
have min.1(one)m height and, if necessary; elbow pipe
should be used after this height. It must have min. 10°
towards the chimney and its length never passes the
0,25 x height of the chimney.
.
Linyitomat Plus Boiler-
Chimney Connection
Example
Electricity and fan
connection
11
siphon