GAS PRESSURE REQUIREMENTS
Correct gas pressure and the use of a properly sized gas supply line is essential for the safe and
efficient performance of this appliance. The inlet and outlet pressures at the control must be
tested on installation, following the procedure over page.
Note: Improper gas pressure will affect heater performance, flame Colour or cause pilot
malfunction.
Natural Gas:
Minimum inlet pressure 1.25 Kpa (5"w.g.)
Maximum inlet pressure 5.0 Kpa (20"w.g.) With supplied inline regulator fitted.
Operating pressure
L.P.G. (NZ Only) and Propane
Minimum inlet pressure 2.75 Kpa (11"w.g.)
Maximum inlet pressure 3.5 Kpa (14"w.g.)
Operating pressure
CAUTION: Do not use this heater if any part has been under water or exposed to moisture
causing corrosion.
A Qualified service technician should inspect the heater and replace any part of the gas
system that has been under water.
25-07-01
1.0 Kpa (4"w.g.)
2.5 Kpa (10"w.g.)
Page 8 of 23
Operation Instructions for Eros Free Standing Gas Fire July 2001.doc