the inputs, also for in this case it is possible to assign a functionality to every single one of the 4 digital
outputs:
Enable on incoming call: (e.g. for additional doorbell)
If this option is selected, the chosen output at any incoming call is enabled for 2 seconds and for example can
be used to trigger an external doorbell or other signaling device.
Use as main door opener: (key button)
If this option is selected, the chosen output will be used as main door opener and connected to the related
symbol in the GUI. The duration of the signal is set by the value explained before.
Use as aux door opener: (lamp button)
If this option is selected, the chosen output will be used as auxiliary door opener and connected to the related
symbol in the GUI. The duration of the signal is set by the value explained before.
Naturally both door opener functions can be configured completely independently (for example, the main
door opener could send out a DTMF tone, meanwhile the aux door opener sends out a KNX command).
Nevertheless, please mention that the configuration menu of the digital in- and outputs is the same for both
main and aux door opener; therefore for every output you will see both options (main and aux door opener).
Note: Please always remember that the explained ports are DIGITAL in- and outputs! Their exact
specifications can be found in the table below. Furthermore it is recommended that both in- and outputs
are always connected through a relay circuit. Corresponding examples can below the mentioned table, with
reference to the pin-out of the DIO connector, as shown on page E-7.
Voltage output HIGH
Voltage outpout LOW
Output current
Example circuit with relay on output 1:
Max. cable lenght of control circuit: < 3m
Example circuit with relay on input 1:
Max. cable lenght of control circuit: < 3m
After the configuration of the desired values the different sub-menus can be closed and – if required – the
settings of the last category can be adapted. This category, named "General Settings", offers different
settings related to the behavior of the app: (See Screenshot on the next page)
3,3V
Voltage input HIGH (= off)
0V
Voltage output LOW (= on)
1,7mA
Load Circuit
Load Circuit
1,65 - 3,6V
0V
Load Circuit
Control Circuit