How To Use The Control Circuit Terminals; Terminal Block Layout; Wiring Instructions - Mitsubishi FR - S500 Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR - S500:
Table of Contents

Advertisement

1

.6 How to Use the Control Circuit Terminals

1

.6.1 Terminal block layout

In the control circuit of the inverter, the terminals are arranged as shown below:
REMARKS
For the cable size, wiring length, etc., refer to the instruction manual (basic).
1

.6.2 Wiring instructions

1) Terminals SD, SE and 5 are common to the I/O signals. These common terminals
must not be earthed.
2) Use shielded or twisted cables for connection to the control circuit terminals and run
them away from the main and power circuits (including the 200V relay sequence
circuit).
3) The input signals to the control circuit are micro currents. When contacts are
required, use two or more parallel micro signal contacts or a twin contact to prevent
a contact fault.
*Information on bar terminals
Introduced products (as of June, 2000): Phoenix Contact Co.,Ltd.
Terminal Screw Size
M3 (A, B, C terminals)
M2
(Other than the above)
Bar terminal crimping terminal: CRIMPFOX ZA3 (Phoenix Contact Co., Ltd.)
CAUTION
When using the bar terminal (without insulation sleeve), use care so that the
twisted wires do not come out.
PC SE
SD SD STF
A
B
C
Terminal screw
size: M3
Bar Terminal Model
(With Insulation
Sleeve)
Al 0.5-6WH
Al 0.75-6GY
Al 0.5-6WH
Terminal arrangement
of control circuit
RUN
10
2
STR
RL RM RH
Terminal screw size: M2
Bar Terminal Model
(Without Insulation
Sleeve)
A 0.5-6
A 0.75-6
A 0.5-6
24
5
4
Japanese version
FM
NA, EC version
<AM>
Wire Size (mm
0.3 to 0.5
0.5 to 0.75
0.3 to 0.5
2
)