Mitsubishi FR - S500 Instruction Manual page 30

Transistorized inverter
Hide thumbs Also See for FR - S500:
Table of Contents

Advertisement

2) "Harmonic suppression guideline for specific consumers"
This guideline sets forth the maximum values of harmonic currents outgoing from a
high-voltage or specially high-voltage consumer who will install, add or renew
harmonic generating equipment. If any of the maximum values is exceeded, this
guideline requires that consumer to take certain suppression measures.
Table 1 Maximum Values of Outgoing Harmonic Currents per 1kW Contract Power
Received Power Voltage
6.6kV
22 kV
33 kV
(1) Application of the harmonic suppression guideline for specific
consumers
New installation/addition/
renewal of equipment
Calculation of equivalent
capacity sum
Not more than
reference capacity
Over reference
capacity
Calculation of outgoing
harmonic current
Harmonic suppression
technique is not required.
5th
7th
3.5
2.5
1.8
1.3
1.2
0.86
Sum of equivalent
capacities
Is outgoing harmonic
current equal to or lower
than maximum value?
Not more than
maximum value
21
11th
13th
17th
1.6
1.3
1.0
0.82
0.69
0.53
0.55
0.46
0.35
Over maximum value
Harmonic suppression
technique is required.
Over
19th
23rd
23rd
0.9
0.76
0.70
0.47
0.39
0.36
0.32
0.26
0.24
1