Output frequency detection

The output frequency detection
signal (FU) is output when the
output frequency reaches or
exceeds the setting. This function
can be used for electromagnetic
brake operation, open signal, etc.
You can also set the detection of
the frequency used exclusively for
reverse rotation.
This function is effective for switching the timing of electromagnetic brake
operation between forward rotation (rise) and reverse rotation (fall) during vertical
lift operation, etc.
Parameter
Name
Output frequency
42
detection
Output frequency
43
detection for reverse
rotation
<Setting>
Refer to the above chart and set the corresponding parameters.
When Pr. 43 "output frequency detection for reverse rotation"
setting applies to forward rotation and the Pr.43 setting applies to reverse rotation.
Use Pr. 64 or Pr. 65 (output terminal function selection) to assign the terminal used
for FU signal output.
CAUTION
Using Pr. 64 or Pr. 65 to change terminal assignment may affect the other functions.
Make setting after confirming the function of each terminal.
Related parameters
Assignment of FU signal to terminal
,
Refer to
Refer to
Refer to
Output
signal
Factory
Setting
6Hz
- - -
Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C
terminal function selection" (refer to page 90)
,
(page 62).
(page 58).
(page 59).
Forward
rotation
ON
OFF
OFF
FU
Setting
Range
0 to 120Hz
0 to 120Hz,
- - -: Same as
- - -
Pr. 42 setting
79
Pr.42
Time
Reverse
rotation
Pr.43
ON
OFF
Remarks
Setting is
enabled
when Pr. 30
= "1".
"- - -", the Pr.42