Combustion Check & Gas Valve Adjusments - E.C.A. Confeo Premix CP 24 HST Installation And User's Operating Instructions

High-efficiency condensing boilers (compatible with externa ldhw tank)
Table of Contents

Advertisement

Combustion Check & Gas Valve Adjusments
- Connect the flue gas analyzer to the sampling point which is located on the air/flue system (in the
elbow, vertical adapter or twin adapter).
- Operate the boiler at maximum load (see page 42, Service Mode).
- Be sure that boiler is running at maximum load (→ maximum fan speed).
- Wait approximately 4 minutes for the stabilization of the values.
- Check the
value against the Table 4.
CO2
- If the CO2 value is not in the range (±0,2), gas valve adjusment is necessary.
- Turn the flow adjustment screw (fig. 31) with 2,5 mm allen key counter-clockwise (in direction
+) to increase or clockwise (in direction -) to decrease gas flow (CO
- Adjust the required CO
- Wait for the stabilization of the values
- Operate the boiler at minimum load (see page 42, Service Mode).
- Be sure that boiler is running at minimum load (→ minimum fan speed).
- Wait approximately 4 minutes for the stabilizaiton of the values.
- Check the
value against the Table 4.
CO2
- If the CO2 value is not in the range (±0,2), gas valve adjusment is necessary.
- Turn the offset adjustment screw (fig. 31) with 2,5 mm allen key clockwise (in direction +) to
increase or counter-clockwise (in direction -) to decrease min. CO
- Adjust the required CO
- Wait for the stabilization of the values.
- Recheck the values at max. load and min. load because each adjustment changes the previous
setting value (fig.30).
Table 4 Checking Values
Boiler Model
Fan Speed (rpm)
Confeo Premix
CP 24 HST
Confeo Premix
CP 30 HST
Table 5 Setting Values
Boiler Model
Fan Speed (rpm)
Confeo Premix
CP 24 HST
Confeo Premix
CP 30 HST
value (±0,1) according to the Table 5.
2
value (±0,1) according to the Table 5.
2
Natural Gas
CO2 (%)
1560
8,7 (±0,2)
4560
9,3 (±0,2)
1560
8,5 (±0,2)
4740
9,0 (±0,2)
Natural Gas
CO2 (%)
1560
8,7 (±0,1)
4560
9,3 (±0,1)
1560
8,5 (±0,1)
4740
9,0 (±0,1)
2
value.
2
O2 (%)
Fan Speed (rpm)
1800
5,6 (±0,3)
4,5 (±0,3)
4320
1860
6,1 (±0,3)
5,1 (±0,3)
4380
O2 (%)
Fan Speed (rpm)
1800
5,6 (±0,2)
4,5 (±0,2)
4320
1860
6,1 (±0,2)
5,1 (±0,2)
4380
value) to the burner.
Propane
CO2 (%)
O2 (%)
5,8 (±0,3)
9,9 (±0,2)
4,4 (±0,3)
10,9 (±0,2)
6,2 (±0,3)
9,7 (±0,2)
4,4 (±0,3)
10,8 (±0,2)
Propane
CO2 (%)
O2 (%)
5,8 (±0,2)
9,9 (±0,1)
4,4 (±0,2)
10,9 (±0,1)
6,2 (±0,2)
9,7 (±0,1)
4,4 (±0,2)
10,8 (±0,1)
40