LED indicator definition
1)
Fault Indicator(red):On indicates when a fault occurred; Off means no fault
2)
Indicator(Green):On means AC is normal, Off means AC is not present,
blinking means voltage is beyond normal range
3)
Inverter Indicator(Green):On : when load is powered by inverter, Off : when it
is not working, blinking: when overload
4)
Bypass Indicator(Green):On : when UPS is in bypass mode, Off: not in bypass
mode; blinking: when the input is beyond normal range
5)
Battery Indicator(Green):On: when UPS is in battery mode, Off : Not in battery
mode; Blinking: when battery voltage is low or battery is not connected
6)
Output Indicator(Green):On: when there is output, Off: no output.
LCD display content
1)
Running parameters
Input voltage/frequency, output voltage/frequency/current, temperature inside
UPS, battery charging/fully charged, battery voltage.
2) Alarm information ( priority from high to low )
Shutting down, auxiliary power fault, output short circuit, inverter fault, rectifier
fault, over temperature, overload, charger fault, battery fault, ready to shut down,
output fault.
3) Parameter setting
Menu setting, floating /boosting charging setting, battery capacity setting, ID of
parallel UPS, output voltage/frequency level/calibration.
 Boosting charging voltage 2.30 to 2.35V per cell floating charging voltage
2.20 to 2.29V per cell
 Battery capacity setting includes the above each battery unit, battery
quantity (8 to 10 )*2, parallel group number, low battery voltage alarm value
(EOD ).
 Parallel setting
 UPS ID setting
 LBS setting ( Enable/Disable, Master/Slave)
- 9 -