Installation; Unpack Checking; Installation Procedure; Installation Note - KStar YDC9300-0.8 User Manual

Table of Contents

Advertisement

2.1 Unpack checking

1)
Don't lean the UPS when moving it out from the packaging.
2)
Check the appearance to see if the UPS is damaged during the transport, do not
switch on the UPS if any damaged found and please contact the dealer.
3)
Check the accessories according to the packing list and contact the dealer if
found any parts missing.

2.2 Installation procedure

2.2.1 Installation note

Put the UPS at flat place next to the equipment.
Keep UPS at least 20cm from wall or equipment or other object. Don't block the
ventilation holes of the UPS front panel and bottom part, so as to keep the
ventilation in good conditions, avoid temperature of components inside getting high.
Keep the UPS away from high temperature, water, flammable gas, erosive gas, dust,
direct sunlight, explosive things
Don't lay the UPS outdoor
3P 125A/400V circuit breaker is required at the input and battery and 2P 125A/400V
is required at the output.
PDU is required to connect to the UPS output so as to weaken the affection between
loads
In order to fix the UPS, please lock its wheels by shifting the sheet on each wheel.
RCD load like computer ,linear load and small inductive load can be connected with
the UPS. Please contact dealer if other types of loads is required to connect.
For the sake of user and equipments, please betake correct power configuration.
2 Installations
Fig.2-1a Correct power configuration
- 18 -

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents