The AL600ULX is a power supply that converts a 115VAC / 60Hz input to a 12VDC or 24VDC regulating output (see
specifications below). The AL600ULX is the base power supply unit for the UL Listed multi-output power supply/charger
series: AL600ULPD4, AL600ULPD4CB, AL600ULPD8, AL600ULPD8CB, AL600ULXPD16, AL600ULXPD16CB
(Refer to AL600ULX Series Power Supply Configuration Reference Chart below).
AL600ULX Series Power Supply Configuration Reference Chart:
Altronix
Model Number
AL600ULX
AL600ULXR
AL600ULXX
AL600ULPD4
AL600ULPD4CB
AL600ULPD8
AL600ULPD8CB
AL600ULXPD16
AL600ULXPD16CB
Do not exceed total output rating of 6 amp per unit.
AL600ULPD4/CB and AL600ULPD8/CB are available in larger enclosure. Add X to the model number
(eg. AL600ULXPD4/CB).
Agency Listings:
• UL Listed for Access Control System Units
(UL 294) and UL Listed Standard for Safety for
Fire Protective Signaling Systems (UL 1481).
• NFPA 72 compliant (Fire-Protective Signaling Service).
Input:
• Input 115VAC / 60Hz, 3.5 amp.
Output:
• 12VDC or 24VDC selectable output(s).
• 6 amp continuous supply current at 12VDC or 24VDC.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
Output
Type
Voltage
Voltage
DC Output
DC
12VDC & 24VDC
- 2 -
- - - - - -
PD4UL
PD4ULCB
PD8UL
PD8ULCB
Two (2) PD8UL
16
Two (2) PD8ULCB
16
Normal
Stand-by Battery
Stand-by
Minimum Operating Time
See Stand-by Specifications pg. 3
Overview:
1
- - - - - -
- - - - - - - - - - - -
6
4
- - - - - -
x - - - - - - 3.5
4
x
- - - - - - - - x
2.5
8
- - - - - -
x - - - - - - 3.5
8
x
- - - - - - x
2.5
- - - - - -
x - - - - - - 3.5
x
- - - - - - x
2.5

Specifications:

Battery Backup (cont'd):
• Automatic switch over to stand-by battery when
AC fails.
• Maximum charge current 0.7 amp.
• Zero voltage drop when switched over to
battery backup.
Supervision:
• AC fail supervision (form "C" contacts).
• Low battery supervision (form "C" contacts).
• Battery presence supervision (form "C" contacts).
Additional Features:
• AC input, DC output and BAT trouble LED indicators.
• Power supply, enclosure, cam lock and battery leads.
• All models are available in red enclosure
(add an "R" suffix to the part # e.g. AL600ULPD8R).
Output Current
Maximum
(alarm)
Altronix Corp.
140 58th St. Brooklyn, NY
California State
Fire Marshal
Factory
NYC Dept.
Mutual
of Buildings
Approved
Stand-by Battery
Minimum Operating Time
UL File # S4707
UL 1481
UL Listed Power
Supplies for
Fire Protective
Signaling
Systems.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
UL 294
UL Listed for
Access Control
System Units.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
"Signal Equipment"
Evaluated to
CSA Standard C22.2
No.205-M1983
Frequency Ripple
Voltage
N/A
300mV
AL600ULX Series