Scc Monitor/Mimic Display Screen; Figure 14 Scc Monitor/Mimic Display Screen - Liebert 1000kVA Operation & Maintenance Manual

100-1000kva, 60hz three phase multi-module
Table of Contents

Advertisement

• Battery Test (MMU Only)—The optional battery test screen allows the operator to perform
manual battery tests to determine the general condition of the battery system. The results of the
last 10 tests are recorded in non-volatile storage and can be retrieved through the battery test
results screen.
• Battery Temp Compensation Charging (MMU Only)—The optional battery temperature
sensing unit, when installed, automatically reduces the float charge voltage in response to
increases in battery temperature. The nominal float voltage is 540VDC (2.25 volts per cell) at
25°C. This float voltage is automatically reduced 5VDC for each temperature rise of 5°C. The LCD
indicates whether the temperature compensation circuit is active.
3.2.2

SCC Monitor/Mimic Display Screen

From SCC Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the
Select pad and the Monitor/Mimic screen is displayed.
The Monitor/Mimic display screen is a simplified block diagram of the UPS system. This screen gives
the operator an overall view of the power flow through the UPS system. The screen consists of three
major sections: the input/UPS metering section, the load metering section and the status and alarm
message areas. The metered parameter values on the Monitor/Mimic screen are updated at one-sec-
ond intervals.

Figure 14 SCC Monitor/Mimic display screen

MOD 1 ON LINE
MOD 2 ON LINE
MOD 3 ON LINE
Input Metering Displays
NOTE
All voltage readings are phase-to-phase measurements (A-B, B-C and C-A). All current
readings are phase measurements (A, B and C).
Item 1 - Bypass Input: This block displays the bypass input voltage and the bypass input frequency.
The System Bypass Breaker is shown to the right of this block. The status of the circuit breaker is
illustrated as open or closed.
Item 2 - UPS Input Pwr: This block displays the input voltage to the UPS modules. This data is
received serially from the modules.
Output Metering Displays
Item 3 - UPS Ratings: The SCC current rating is specified at the top of this block. The UPS system
output voltage and frequency are also displayed in this block. The UPS Output Breaker is shown to
the right of this block. The status of the circuit breaker is illustrated as open or closed.
Item 4 - Load: This block displays the total output power to the critical load in kVA and kW. The
critical load current per phase is also displayed in this block. Note that kW is not displayed when the
load is on the bypass line.
The load block also indicates the number of modules connected and whether the UPS system is oper-
ating in the redundant or non-redundant mode.
During an overload condition, the time remaining before shutdown or transfer is displayed at the bot-
tom of the load box.
1
BYPASS INPUT
A-B
B-C
C-A
480V 480V 480V
60.0 Hz
2
UPS INPUT PWR
A-B
B-C
C-A
480V 480V 480V
5
OK to Transfer
Static Switch Connected
4
© 1989-2003
3
UPS RATINGS
SCCB 1600
OUTPUT VOLTAGE
A-B
B-C
C-A
480V
480V
480V
60.0 Hz
7
6
28
LOAD
627 KVA / 502 KW
A
B
C
755A
755A
755A
3 OF 3 MODULES
CONNECTED
REDUNDANT
Operation

Advertisement

Table of Contents
loading

This manual is also suitable for:

Series 610

Table of Contents