Inch Concentric Termination Installation - State Water Heaters SUF 130 300 Instruction Manual

Commercial gas water heaters 100-101 series
Hide thumbs Also See for SUF 130 300:
Table of Contents

Advertisement

4 INCH CONCENTRIC TERMINATION INSTALLATION

INTAKE AIR CONNECTION
3 INCH PVC
3" x 3" x 4"
Y FITTING
VENT CONNECTION - 3 INCH PVC
VENT PIPE IS 2 1/2 INCH SDR-26 PIPE
SUPPLIED LENGTH 37 INCHES (94 cm)
MAXIMUM ALLOWABLE LENGTH 73 INCHES (185 cm)
MINIMUM ALLOWABLE LENGTH 25 INCHES (64 cm)
INTAKE AIR PIPE IS 4 INCH SDR-26 PIPE
SUPPLIED LENGTH 24 INCHES (60 cm)
MAXIMUM ALLOWABLE LENGTH 60 INCHES (152 cm)
MINIMUM ALLOWABLE LENGTH 12 INCHES (30 cm)
INTAKE AIR PIPE
Y FITTING ASSEMBLY
VENT PIPE ASSEMBLY
4 INCH CONCENTRIC TERMINATION KIT
FOUR PIECE KIT - FIELD ASSEMBLY REQUIRED
Figure 26
1.
2.
3.
metal strapping or equivalent support materials.
4.
5.
6.
7.
8.
9.
INTAKE AIR PIPE
VENT PIPE
VENT CAP
VENT CAP
COMBUSTION
AIR
ROOF FLASHING
(field supplied)
VENT
PIPE
4 INCH CONCENTRIC TERMINATION
VERTICAL INSTALLATION
NOTE: SECURING STRAP MUST BE
FIELD INSTALLED TO PREVENT
MOVEMENT OF TERMINATION KIT
IN SIDEWALL.
STRAP
VENT
(field supplied)
PIPE
INTAKE
AIR PIPE
4 INCH CONCENTRIC TERMINATION
SIDEWALL INSTALLATION
28
VENT
MAINTAIN 12" (30 cm)
18" (45 cm) FOR CANADA
MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED
SNOW LEVEL. MAXIMUM OF
24" (60 cm) ABOVE ROOF.
STRAP
(field supplied)
NOTE: SECURING STRAP
MUST BE FIELD INSTALLED
TO PREVENT MOVEMENT
OF TERMINATION KIT
INTAKE
AIR PIPE
Figure 27
COMBUSTION
AIR
1 INCH
MAXIMUM
Figure 28
VENT

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Suf 130 500Suf 130 400

Table of Contents