State Water Heaters SUF 130 300 Instruction Manual page 25

Commercial gas water heaters 100-101 series
Hide thumbs Also See for SUF 130 300:
Table of Contents

Advertisement

on page 25.
6.
7.
pass through the roof.
NOTE:
through the roof.
8.
2" (5 cm)
MAXIMUM
FIELD
SUPPLIED
90° ELBOW
FIELD SUPPLIED
PLUMBING
ROOF BOOT
OR FLASHING
FIELD
SUPPLIED
STRAP/SUPPORT
VERTICAL TERMINATION(S) INSTALLATION
INTAKE AIR AND/OR VENT (EXHAUST)
Figure 19
9.
FACTORY SUPPLIED
STANDARD TERMINATION
POINTED DOWN TOWARDS
THE GROUND
MAINTAIN 12" (30 cm)
18" (45 cm) FOR CANADA
MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED
SNOW LEVEL.
10.
IF LESS THAN
10 FEET (3 m)
24 INCHES (60 cm)
MINIMUM HEIGHT ABOVE
INTAKE AIR AND/OR VENT
TERMINATION(S) MUST BE A
MINIMUM OF 24 INCES (60 cm)
ABOVE ANY PARAPET, VERTICAL
WALL OR STRUCTURE WITHIN
10 FEET (3 m) HORIZONTALLY.
VERTICAL TERMINATION(S) FLAT ROOF CLEARANCE
INTAKE AIR AND/OR VENT (EXHAUST)
11.
24 INCHES (61 cm) MINIMUM
48 INCHES (122 cm) IN COLDER CLIMATES
FIELD
SUPPLIED
90° ELBOW
VENT (EXHAUST)
TERMINATION
FACTORY SUPPLIED
STANDARD TERMINATIONS
POINTED DOWNWARD
FIELD SUPPLIED
PLUMBING
ROOF BOOTS
OR FLASHINGS
VERTICAL TERMINATION - DIRECT VENT
STANDARD TERMINATIONS
25
Figure 20
INTAKE AIR
TERMINATION
MAINTAIN 12" (30 cm)
18" (45 cm) FOR CANADA
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW LEVEL.
Figure 21