6 INCH CONCENTRIC TERMINATION INSTALLATION
6" x 4" STANDARD
INTAKE AIR CONNECTION
REDUCER BUSHING
6" or 4" PVC
VENT PIPE
VENT
6" x 4" NO STOP-LIP
CONNECTION
REDUCER BUSHING
4" PVC
VENT PIPE IS 4 INCH SCHEDULE 40 PVC
SUPPLIED LENGTH 46 1/2 INCHES (118 cm)
MAXIMUM ALLOWABLE LENGTH 66 1/2 INCHES (169 cm)
MINIMUM ALLOWABLE LENGTH 33 1/8 INCHES (84 cm)
INTAKE AIR PIPE IS 6 INCH SCHEDULE 40 PVC
SUPPLIED LENGTH 25 3/8 INCHES (64 cm)
MAXIMUM ALLOWABLE LENGTH 45 3/8 INCHES (115 cm)
MINIMUM ALLOWABLE LENGTH 12 INCHES (30 cm)
6 INCH CONCENTRIC TERMINATION KIT
SEVEN PIECE KIT - FIELD ASSEMBLY REQUIRED
Figure 29
1.
2.
3.
4.
5.
6.
metal strapping or equivalent support materials.
7.
8.
9.
10.
the terminal.
INTAKE AIR PIPE
6" x 6" x 6"
VENT TERMINAL
Y FITTING
WITH SCREEN
VENT CAP
STAINLESS STEEL
INTAKE AIR PIPE
Y FITTING ASSEMBLY
VENT CAP
VENT PIPE ASSEMBLY
11.
COMBUSTION
AIR
ROOF FLASHING
(field supplied)
INTAKE
AIR PIPE
6 INCH CONCENTRIC TERMINATION
VERTICAL INSTALLATION
NOTE: SECURING STRAP MUST BE
FIELD INSTALLED TO PREVENT
MOVEMENT OF TERMINATION KIT
IN SIDEWALL.
STRAP
(field supplied)
VENT
PIPE
INTAKE
AIR PIPE
6 INCH CONCENTRIC TERMINATION
SIDEWALL INSTALLATION
12.
13.
29
VENT
MAINTAIN 12" (30 cm)
18" (45 cm) FOR CANADA
MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED
SNOW LEVEL. MAXIMUM OF
24" (60 cm) ABOVE ROOF.
STRAP
(field supplied)
NOTE: SECURING STRAP
MUST BE FIELD INSTALLED
TO PREVENT MOVEMENT
OF TERMINATION KIT
VENT
PIPE
Figure 30
COMBUSTION
AIR
1 INCH
MAXIMUM
Figure 31
VENT