Functions of the DHW circuit
ated prematurely if the remaining time until the disinfection temperature is reached is shorter
than the adjusted 'Duration'. The error message is automatically reset when the disinfection
temperature is properly reached during the following thermal disinfection cycle.
Thermal disinfection for preventing legionella infection causes:
− Excessively high return flow temperatures during the disinfection cycle (return flow tem-
perature limitation suspended)
− Excessively high DHW temperatures after thermal disinfection has been concluded
− Possibly lime scale, which can have a negative effect on heat exchanger performance.
Note:
This function is not available when a storage tank thermostat is used.
Functions
Storage tank sensor 1
Thermal disinfection
98
WE
Configuration
1
CO4 > F01 - 1
0
CO4 > F14 - 1
Wednesday
Monday, Tuesday, ..., daily
00:00 - 04:00
Time: Adjustable as required in steps of 15 minutes
70.0 °C
Disinfection temperature: 60.0 to 90.0 °C
10.0 °C
Boost: 0 to 50 °C
0 min
Duration: 0 to 255 min
ON
Active when BI =: ON, OFF (start of disinfection
with terminal 03/12 = ON, OFF; only applies when
Start time = Stop time)