Automation system and heating and district heating controller
Table of Contents

Advertisement

Note:
− The controller starts to write over the oldest data as soon the memory of the data
logging module is full after approximately eight days. The current memory capacity
of the data logging module can be read in the extended operating level under 'Log-
ging memory' as the second value in the sequence (range of values: 0 to 6035). Di-
rectly after inserting the data logging module, data can be first read after the first
scanning cycle has been performed.
− The internal memory of the controller is full after approx. 14 days. After that, the
controller starts to write over the oldest data.
The data log viewer software allows the data to be viewed in graph format. The USB convert-
er 3 (order no. 1400-9377) is required to connect the data logging module to a computer.
The data log viewer software is supplied together with the USB converter 3.
EB 5573-1 EN
Communication
123