Appendix
P
Parameters
07 Max. flow temperature
09 Outdoor temperature for continuous
day mode
10 Minimum flow temperature set point
HC for binary demand processing
11 Return flow gradient
12 Return flow level
13 Base point for return flow temperature:
14 Max. return flow temperature
15 Set point boost (pre-control circuit)
21 Start speed reduction
21 Stop speed reduction
21 Min. speed signal
CO1 function block parameters (heating circuit HC1) and CO2 function block parameters
(heating circuit HC2)
F
Function block parameters
03 KP (limiting factor)
05 Start temperature
05 Temp. rise/day
05 Maximum temperature
05 Duration:
05 Temp. reduction/day
09 Cycle time
09 KP (gain)
12 KP (gain)
12 Tn (reset time)
12 TV (derivative-action time)
12 TY (valve transit time)
12 Hysteresis
12 Min. ON time
12 Min. OFF time
154
PA1 (HC1)
PA2 (HC2)
CO1 (HC1)
CO2 (HC2)
Value range
–5.0 to 150.0 °C
–50.0 to 5.0 °C
5.0 to 150.0 °C
0.2 to 3.2
–30.0 to 30.0 °C
5.0 to 90.0 °C
5.0 to 90.0 °C
0.0 to 50.0 °C
5.0 to 90.0 °C
5.0 to 90.0 °C
0 to 10 V
Value range
0.1 to 10.0
20.0 to 60.0 °C
0.0 to 10.0 °C
25.0 to 60.0 °C
0 to 10 days
0.0 to 10.0 °C
0 to 100 min
0.0 to 25.0
0.1 to 50.0
1 to 999 s
0 to 999 s
5 to 240 s
1.0 to 30.0 °C
0 to 10 min
0 to 10 min
EB 5573-1 EN