Flow rate limitation in RK1
Flow rate limitation in RK2
Capacity limitation
All necessary function block parameters to set up the capacity limitation are available in
CO6 > F12 or CO6 > F14 for systems with two control valves. One after the other, the sys-
tem's max. limit or max. limit for heating and the max. limit for DHW for systems with only
one control valve and secondary DHW heating have to be set. The 'Limiting factor' deter-
mines how strongly the controller responds when the limit values are exceeded in either di-
rection.
NOTICE
If the controller indicates CO5 > F00 - 1, any access to the return flow, flow rate and
capacity settings is locked.
Functions
Meter bus
Capacity limitation in RK1
Capacity limitation in RK2
120
WE
Configuration
0
CO6 > F11 - 1
1.5 m³/h
Max. limit: At, 0.01 to 650 m³/h
1.5 m³/h
Max. limit for heating: At, 0.00 to 650 m³/h
1.5 m³/h
Max. limit for DHW: 0.01 to 650 m³/h
1.0
Limiting factor: 0.1 to 10.0
0
CO6 > F13 - 1
1.5
Max. limit: 0.01 to 650
1.0
Limiting factor: 0.1 to 10.0
* TROVIS 5573-100x: WMZ1...6; TROVIS 5573-110x: WMZ1...3
WE
Configuration
0
CO6 > F10 - 1
255
WMZ1...x address*: 0 to 255
1434
WMZ1...x model code*: 1434, CAL3, APAtO, SLS
24h
WMZ1...x reading mode*: 24h, CONT, CoiL
0
CO6 > F12 - 1
1.5 kW
Max. limit: At, 0.1 to 6500 kW
1.5 kW
Max. limit for heating: At, 0.0 to 6500 kW
1.5 kW
Max. limit for DHW: 0.1 to 6500 kW
1.0
Limiting factor: 0.1 to 10.0
0
CO6 > F14 - 1
1.5 kW
Max. limit: 0.01 to 6500 kW
1.0
Limiting factor: 0.1 to 10.0
* TROVIS 5573-100x: WMZ1...6; TROVIS 5573-110x: WMZ1...3