Samson TROVIS 5500 Mounting And Operating Instructions page 147

Automation system and heating and district heating controller
Table of Contents

Advertisement

PA4: Domestic hot water heating (DHW)
P
Display reading
01
02
03
04
05
06
07
10
11
12
PA5: System-wide parameters
P
Display reading
01
02
EB 5573-1 EN
Parameter: Value range (default setting)
Min. adjustable DHW set point:
5.0 to 90.0 °C (40.0 °C)
Max. adjustable DHW set point:
5.0 to 90.0 °C (90.0 °C)
Hysteresis:
1.0 to 30.0 °C (5.0 °C)
Charging temperature boost:
0.0 to 50.0 °C (10.0 °C)
Max. charging temperature (only with CO4 > F05 - 1):
20.0 to 150.0 °C (80.0 °C)
Lag time for storage tank charging pump = Valve transit time x
P06:
0.0 to 10.0 (1.0)
Max. return flow temperature:
20.0 to 90.0 °C (65.0 °C)
Solar circuit pump ON:
1.0 to 30.0 °C (10.0 °C)
Solar circuit pump OFF:
0.0 to 30.0 °C (3.0 °C)
Max. storage tank temperature:
20.0 to 90.0 °C (80.0 °C)
Parameter: Value range (default setting)
Start temperature for boiler pump (system Anl 16.x only)
20.0 to 90.0 °C (60.0 °C)
Boiler pump hysteresis (system Anl 16.x only)
0.0 to 30.0 °C (5.0 °C)
Appendix
147