EB 5573-1 EN
q Select F20 configuration.
¼ Activate editing mode for configuration.
The currently active configuration '0' or '1' is shown in-
verted on the display.
q Activate function block ('1').
¼ Confirm activation.
¼ Select the temperature that you want to calibrate.
¼ Open calibration.
The temperature is shown inverted on the display.
¼ Correct measured value.
Read the actual temperature directly from the thermome-
ter at the point of measurement and enter this value as
the reference temperature.
¼ Confirm corrected measured value.
¼ Proceed in the same manner to calibrate further sensors.
Exit configuration level:
q Select 'Back'.
q Exit configuration level.
Turn the rotary switch back to
Operation
(operating level).