Appendix
CO5: System-wide functions (all systems)
If the controller indicates CO5 > F00 - 1, any access to the return flow, flow rate and capaci-
ty settings is locked.
F
Function
01 Sensor type
02
03
04 Summer mode
05 Delayed
outdoor
temperature
adaptation
(decreasing)
06 Delayed
outdoor
temperature
adaptation
(increasing)
07 Error indication
08 Summer time
09 Frost protection
140
Comments
WE
System
Function block parameters: value range (default setting)
1
Independent of the function block setting Pt 1000
All*
0
CO5 > F04 - 1: Summer mode
Not Anl
1.5, 1.6,
Function block parameters:
1.9, 3.5
Time: Adjustable as required (01.06. - 30.09.)
No. days until activation: 1 to 3 (2)
No. days until deactivation: 1 to 3 (1)
Limit: 0.0 to 30.0 °C (18.0 °C)
0
CO5 > F05 - 1: Delayed outdoor temperature adaptation as
Not Anl
1.9
the temperature falls
Function block parameters:
Delay/h: 1.0 to 6.0 °C (3.0 °C)
0
Not system
CO5 > F06 - 1: Delayed outdoor temperature adaptation as
Anl 1.9
the temperature rises
Function block parameters:
Delay/h: 1.0 to 6.0 °C (3.0 °C)
0
CO5 > F07 - 1: Terminal for error indication (see table in sys-
Not Anl
4.1, 4.5,
tem schematics)
11.1,
Function block parameters:
11.2,
Relay contact: NO contact, NC contact (NO contact)
11.3,
11.6,
16.1, 16.6
0
CO5 > F08 - 1: Summer/standard time switchover
All
1
Not sys-
CO5 > F09 - 1: Highest priority for frost protection
tems Anl
Function block parameters:
1.5, 1.6,
Limit: –15.0 to 3.0 °C (3.0 °C)
1.9, 3.5
CO5 > F09 - 0: Restricted frost protection
Function block parameters:
Limit: –15.0 to 3.0 °C (3.0 °C)
0
1.5, 1.6,
1.9, 3.5