Samson TROVIS 5500 Mounting And Operating Instructions page 143

Automation system and heating and district heating controller
Table of Contents

Advertisement

F
Function
13 Flow rate
limitation in
RK2
14 Capacity
limitation in
RK2
F Function block number, WE Default setting, Anl System code number
CO8 > Initialization of BI1 and BI2 (all systems)
F
Function
01 Analysis of BI1
02 Analysis of BI2
EB 5573-1 EN
Comments
WE
System
Function block parameters: value range (default setting)
0
Anl 3.0,
CO6 > F13 - 1: Flow rate limitation (only with CO6 > F10 - 1
4.x, 10.0,
and when WMZ2 is activated)
11.x
Function block parameters:
Max. limit/0.01 to 650 m³/h (1.5 m³/h)
Limiting factor/0.1 to 10 (1)
0
Anl 3.0,
CO6 > F14 - 1: Capacity limitation (only with CO6 > F10 - 1
4.x, 10.0,
and when WMZ2 is activated)
11.x
Function block parameters:
Max. limit/0.1 to 6500 kW (1.5 kW)
Limiting factor/0.1 to 10 (1)
* Not systems Anl 1.0, 1.5–1.9, 3.0, 3.5, 4.0, 10.0, 11.x
Comments
WE
System
Function block parameters: value range (default setting)
0
All
CO8 > F01 - 1: Analysis active
Function block parameters:
Error message when BI = 0, BI = 1, none (1)
0
CO8 > F02 - 1: Analysis active
All
Function block parameters:
Error message when BI = 0, BI = 1, none (1)
Appendix
143