Samson TROVIS 5500 Mounting And Operating Instructions page 142

Automation system and heating and district heating controller
Table of Contents

Advertisement

Appendix
CO6 > Modbus (all systems)
F
Function
01 Modbus
02 16-bit address
03 Modem
04 Automatic con-
figuration
05 Lock dial-up to
building auto-
mation system
06 Dial-up also
upon corrected
error
07 Monitoring
08 Text message
10 Meter bus
(TROVIS 5573-
100x only with
optional Mod-
bus/meter bus
gateway)
11 Flow rate
limitation in
RK1
12 Capacity
limitation in
RK1
142
Comments
WE
System
Function block parameters: value range (default setting)
1
CO6 > F01 - 1: Modbus active
All
0
CO6 > F02 - 1: Modbus 16-bit addressing
All
(only with CO6 > F01 - 1)
CO6 > F02 - 0: Modbus 8-bit addressing
0
CO6 > F03 - 1: Modem function
All
(only with CO6 > F01 - 1 and CO6 > F08 - 1)
0
CO6 > F04 - 1: Automatic modem configuration
All
(only with CO6 > F03 - 1 and CO6 > F08 - 1)
0
CO6 > F05 - 1: Lock dial-up to building automation system
All
(only with CO6 > F03 - 1)
0
CO6 > F06 - 1: Dial-up to building automation system also to
All
indicate that an error has been corrected (only when CO6 >
F03 - 1)
0
CO6 > F07 - 1: Control system monitoring > Resets all level bits
All
to "autonomous" when there is no communication(only with
CO6 > F01 - 1)
0
All
CO6 > F08 - 1: Text message function active
0
CO6 > F10 - 1: Meter bus active
All
Function block parameters:
WMZ1...x address*/0 to 255 (255)
WMZ1...x model code*/1434, CAL3, APAtO, SLS (1434)
WMZ1...x reading mode*/24h, CONT, CoiL (24 h)
* TROVIS 5573-100x: WMZ1...6; TROVIS 5573-110x: WMZ1...3
0
CO6 > F11 - 1: Flow rate limitation (only with CO6 > F10 - 1
Not Anl
1.9
and when WMZ1 is activated)
Function block parameters:
Max. limit/At, 0.01 to 650 m³/h (1.5 m³/h)
Max. limit for heating*/At, 0.00 to 650 m³/h (1.5 m³/h)
Max. limit for DHW*/0.01 to 650 m³/h (1.5 m³/h)
Limiting factor/0.1 to 10 (1)
0
Not Anl
CO6 > F12 - 1: Capacity limitation (only with CO6 > F10 - 1
1.9
and when WMZ1 is activated)
Function block parameters:
Max. limit/At, 0.1 to 6500 kW (1.5 kW)
Max. limit for heating*/At, 0.0 to 6500 kW (1.5 kW)
Max. limit for DHW*/0.1 to 6500 kW (1.5 kW)
Limiting factor/0.1 to 10 (1)