Samson TROVIS 5500 Mounting And Operating Instructions page 145

Automation system and heating and district heating controller
Table of Contents

Advertisement

P
Display reading
06
07
09
10
11
12
13
14
15
PA2: Heating circuit HC2
P
Display reading
01
02
03
EB 5573-1 EN
Parameter: Value range (default setting)
Min. flow temperature:
–5.0 to 150.0 °C (20.0 °C)
Max. flow temperature:
–5.0 to 150.0 °C (90.0 °C)
–5.0 to 50.0 °C (50.0 °C) with CO1 > F05 - 1
Outdoor temperature for continuous day mode:
–50.0 to 5.0 °C (–15 °C)
Minimum flow temperature set point HC for binary demand
processing:
5.0 to 150.0 °C (40.0 °C)
Return flow gradient:
0.2 to 3.2 (1.2)
Return flow level:
–30.0 to 30.0 °C (0.0 °C)
Base point for return flow temperature:
5.0 to 90.0 °C (65.0 °C)
Max. return flow temperature:
5.0 to 90.0 °C (65.0 °C)
Set point boost (pre-control circuit):
0.0 to 50.0 °C (5.0 °C)
Parameter: Value range (default setting)
Flow gradient:
0.2 to 3.2 (1.8)
0.2 to 1.0 (1.0) with CO1, 2 > F05 - 1
Level (parallel shift):
–30.0 to 30.0 °C (0.0 °C)
Flow set point (day) (only with CO1 > F02 - 0 and CO1 >
F09 - 1):
–5.0 to 150.0 °C (50.0 °C)
Appendix
145