Samson TROVIS 5500 Mounting And Operating Instructions page 134

Automation system and heating and district heating controller
Table of Contents

Advertisement

Appendix
F
Function
18 External
demand
20 Demand for
external heat
21 Speed
reduction of
charging pump
based on
charging
progress
F Function block number, WE Default setting, Anl System code number
CO2: RK2 · Heating circuit 2 (systems Anl 3.x, 4.x and 10.0, 16x)*
F
Function
01 Room sensor
03 Return flow
sensor
04 Cooling control
134
Comments
WE
System
Function block parameters: value range (default setting)
0
All*
CO1 > F18 - 1: External demand 0 to 10 V
The standardized signal output (terminals 11/12) is not avail-
able anymore as a control output. The maximum flow set point
(with boost, if applicable) is demanded as a 0 to 10 V signal at
the standardized signal output.
Function block parameters:
Lower transmission range: 0.0 to 130.0 °C (0.0 °C)
Upper transmission range: 0.0 to 130.0 °C (120.0 °C)
Boost: 0.0 to 30.0 °C (0.0 °C)
0
CO1 > F20 - 1: External demand for heat due to insufficient heat
All
supply
0
CO1 > F21 - 1: Activation of speed reduction
16.x
Function block parameters:
Start speed reduction: 5 to 90 °C (40 °C)
Stop speed reduction 5 to 90 °C (50 °C)
Min. speed signal: 0 to 10 V (2 V)
Comments
WE
System
Function block parameters: value range (default setting)
0
CO2 > F01 - 1: Room sensor RF2, temperature reading and
All*
FG1 input for Type 5257-5 Room Panel active
0
CO2 > F03 - 1: Return flow sensor RüF2; limitation function ac-
10.x, 16.x
tive
1
3.0, 4.x
Function block parameters:
KP (limiting factor): 0.1 to 10.0 (1.0)
0
CO2 > F04 - 1: Cooling control, only with CO2 > F11 - 1
All*
The cooling control function causes a reversal of the operating
direction and a minimum limitation of the return flow tempera-
ture in RK1.
EB 5573-1 EN