Samson TROVIS 5500 Mounting And Operating Instructions page 146

Automation system and heating and district heating controller
Table of Contents

Advertisement

Appendix
P
Display reading
04
05
06
07
09
11
12
13
14
146
Parameter: Value range (default setting)
Flow set point (night) (only with CO1 > F02 - 0 and CO1 >
F09 - 1):
–5.0 to 150.0 °C (30.0 °C)
Four-point characteristic
Outdoor temperature:
–50.0 to 50.0 °C (–15.0 °C, –5.0 °C, 5.0 °C, 15.0 °C)
with CO2 > F04 -1: (5 °C, 15 °C, 25 °C, 30 °C)
Flow temperature:
–5.0 to 150.0 °C (70.0 °C, 55.0 °C, 40.0 °C, 25.0 °C)
with CO2 > F04 -1: (20 °C, 15 °C, 10 °C, 5 °C)
Reduced flow temperature:
–5.0 to 150.0 °C (60.0 °C, 40.0 °C, 20.0 °C, 20.0 °C)
with CO2 > F04 -1: (30 °C, 25 °C, 20 °C, 15 °C)
Return flow temperature:
5.0 to 90.0 °C (65.0 °C, 65.0 °C, 65.0 °C, 65.0 °C)
Min. flow temperature:
–5.0 to 150.0 °C (20.0 °C)
Max. flow temperature:
–5.0 to 150.0 °C (90.0 °C)
–5.0 to 50.0 °C (50.0 °C) with CO1 > F05 - 1
Outdoor temperature for continuous day mode:
–50.0 to 5.0 °C (–15 °C)
Return flow gradient:
0.2 to 3.2 (1.2)
Return flow level:
–30.0 to 30.0 °C (0.0 °C)
Base point for return flow temperature:
5.0 to 90.0 °C (65.0 °C)
Max. return flow temperature:
5.0 to 90.0 °C (65.0 °C)
EB 5573-1 EN