Samson TROVIS 5500 Mounting And Operating Instructions page 141

Automation system and heating and district heating controller
Table of Contents

Advertisement

F
Function
12 Creep feed rate
limitation
14 Operation UP1
15 Release
16 Return flow
temperature
limitation
(proportional
controller)
19 Monitoring
20 Sensor calibra-
tion
21 Lock manual
level
22 Lock rotary
switch
23 0 to 10 V
signal for
outdoor
temperature
F Function block number, WE Default setting, Anl System code number
EB 5573-1 EN
Comments
WE
System
Function block parameters: value range (default setting)
0
Not Anl
CO5 > F12 - 1: Creep feed rate limitation
1.9
Function block parameters:
Switching mode: Binary, analog (binary)
Active when BI = ON, OFF (ON)
0
CO5 > F14 - 1: Feeder pump UP1 operation to cover own de-
All
mand
Note: the feeder pump UP1 also starts to operate to cover the
demand of RK2.
0
CO5 > F15 - 1: Release controller at BI1
All
Function block parameters:
Active when BI = ON, OFF (ON)
0
CO5 > F16 - 1: Return flow temperature limitation with P algo-
All
rithm
0
CO5 > F19 - 1: Temperature monitoring
All
1
CO5 > F20 - 1: Set all sensor calibration values
All
CO5 > F20 - 0: Delete all sensor calibration values
0
All
CO5 > F21 - 1: Lock rotary switch
In
0
All
CO5 > F22 - 1: Lock rotary switch
Key number input is still possible.
0
All
CO5 > F23 - 1: Outdoor temperature received or sent as 0 to
10 V signal (terminals 11/12)
Function block parameters:
Direction: Input, Output (Input)
Lower transmission range: –30.0 to 100.0 °C (–20.0 °C)
Upper transmission range: –30.0 to 100.0 °C (50.0 °C)
switch position, the controller runs in automatic mode
Appendix
141