Appendix 2: Tec-Eye Architecture - Bard D36A2P/BLD.10304 Installation And Service Instructions Manual

Replacement parts manual dc free cooling unit system two (2) d-series dual-tec™ wall-mounted package one (1) bard-linktm plc lead/lag controller controller models lc1000-100/bld.10293, lc1500-100/bld.10291
Table of Contents

Advertisement

CAUTION: The Bard DC-FCU System has been pre-programmed with what is widely considered to be the best
settings for efficiency and operation. Any changes to internal programming through the LC-Series Controller or the
TEC-EYE not covered within this manual may cause the systems to operate improperly, cause internal damage to
the HVAC units, cause the shelter to overheat, or other very serious consequences. Although complete controller
programming architecture for both the LC-Controller and TEC-EYE has been provided, going outside the boundaries
of what has been covered in this manual not recommended.
Screen
The Status screen is the default screen on startup, and
Status Screen
anytime more than 5 minutes has elapsed from last change.
(Use UP/DOWN arrow keys to scroll)
RAT
SAT
OAT
OAH
Dewpoint
Blower
Damper
Master Control
Status
Main Menu screen(s) allows access to operational
Main Menu
programming, access by pressing MENU key at any time.
(MENU key to enter, use UP/DOWN arrow keys to scroll)
On/Off Unit
Unit Address
Power by Display On/Off
Status
Setpoint
Cooling Setpoint
Heating Setpoint
Cooling Stg. Diff.
Heating Stg. Diff.
FreeCool
FreeCool Enable
Differential
DC OA-Return Diff.
Supply Temp Low Limit
Damper Time
Runtest Time
Freeze Temp Low Limit

APPENDIX 2: TEC-EYE ARCHITECTURE

Menu Item
°F
°F
°F
%
°F
Off/On
%
Master Control
Unit On
1
On
All setpoint changes are
limited to 60 minutes
77°F
60°F
5°F
2°F
55°F
50°F
10°F
10°F
45°F
150 seconds
76 seconds
30°F
Value
Displays current data
Current return air temperature
Current supply Air temperature
Current outdoor air temperature
Current outdoor air humidity
Current temperature of dewpoint
Displays status of blower
Displays percentage of current opening
Current operational status, "Running
Stand Alone" if communication lost
D-Series controller board is currently
active, "Off by Keyboard" if disabled by
TEC-EYE
Physical address of controller
"OFF by Keyboard" system has been
turned off at controller
Time alloted before damper fail is
realized
Temperature sensed by Freezestat
which initiates compressor shutdown
Description
Manual 2100-620A
Page
99 of 107