Figure 2.23 Verifying Incoming Voltage; Manual 2100-620A - Bard D36A2P/BLD.10304 Installation And Service Instructions Manual

Replacement parts manual dc free cooling unit system two (2) d-series dual-tec™ wall-mounted package one (1) bard-linktm plc lead/lag controller controller models lc1000-100/bld.10293, lc1500-100/bld.10291
Table of Contents

Advertisement

Shelter supply breaker in ON position Bard
system breaker in OFF position

Manual 2100-620A

Page
68 of 107
FIGURE 2.23
Verifying Incoming Voltage: VDC
Multimeter set to VDC
Displayed voltage must be within this range
52VDC
48VDC Shelter System
Voltage Range:
40VDC – 56VDC
Typical Running Range:
48VDC – 53VDC