Before connecting the external alarm wiring, identify the model of the controller (see label on inside of controller door. The
connections described below are for the LC1500-100 controller only.
The LC1500-100 has the same eight (8) separate series of normally closed dry contacts as the LC1000-100, but has a
prewired 66 punch-down block to make external connections easier.
• Smoke
• Generator
• Hydrogen
• Lag Unit Run
Field wiring for alarms
48" umbilical cord allows for mounting the 66 punch-down
block to either side, top or bottom of PLC controller cox.
Bridge clips have been inserted for convenience.
* There is no longer any need for the electro-mechanical coiled-bulb type thermostats—like the Johnson Penn A19-
Series—for High/Low Temperature Alarms. Do not install in new sites, and remove them in retrofit applications.
FIGURE 1.20
LC1500-100 External Alarm Wiring
• High Temp*
• HVAC 1 Fail
• Low Temp*
• HVAC 2 Fail
Manual 2100-620A
Page
27 of 107